"State
Specific Zones (not REScheck zones)"

|
To
find out what zone your county is in
click on your state below:
|
|
|
|
REScheck
was developed by Pacific Northwest National Labs (PNNL) as a fairly
easy way to see if homes meet the Model Energy Code.
|
Do
You Want to Look at REScheck Prescriptive Packages
for a zone?
|
|
|
If you are unsure
which county is in which zone
click
here
|
|
Examples
of Code Compliant Residential Insulation Levels
|
|
MININUM
INSULATION R VALUES
|
MAXIMUM
WINDOW & DOOR AREA
|
|
ZONE
|
CEILING
|
WALL
|
FLOOR
|
BASEMENT
|
MININUM
EFFICIENCY
HEATING
ANDCOOLING
|
HIGH COOLING
ONLY
|
HIGH
HEATING
ONLY
|
HIGH EFFICIENCY
HEATING &COOLING
|
|
|
|
|
|
|
|
|
|
| DOUBLE
PANE METAL WITH THERMAL BREAK (U = 0.67 R = 1.49) |
| 1
[1900 HDD] |
30
|
13
|
19
|
5
|
23.2% |
27% |
30.4% |
34.2% |
| 2
[2500 HDD] |
30
|
13
|
19
|
5
|
19.6% |
22.5% |
26.9% |
29.8% |
| 3
[3500 HDD] |
30
|
13
|
19
|
5
|
11.9% |
13.3% |
18.8% |
20.2% |
| 4
[4500 HDD] |
30
|
13
|
19
|
7
|
9.3% |
10.4% |
16.0% |
17.2% |
|
|
|
|
|
|
|
|
|
| DOUBLE
PANE WOOD OR VINYL (U = 0.56 R = 1.79 ) |
| 1
[1900 HDD] |
30
|
13
|
19
|
5
|
28.5% |
33.3% |
37.4% |
42.4% |
| 2
[2500 HDD] |
30
|
13
|
19
|
5
|
24.2% |
27.7% |
33.2% |
36.7% |
| 3
[3500 HDD] |
30
|
13
|
19
|
5
|
14.7% |
16.4% |
23.2% |
24.9% |
| 4
[4500 HDD] |
30
|
13
|
19
|
7
|
11.4% |
12.8% |
19.8% |
21.2% |
|
|
|
|
|
|
|
|
|
| DOUBLE
PANE WOOD OR VINYL, LOW-E ( U = 0.52 R = 1.92) |
| 1
[1900 HDD] |
30
|
13
|
19
|
5
|
31.2% |
36.3% |
40.9% |
46.0% |
| 2
[2500 HDD] |
30
|
13
|
19
|
5
|
26.4% |
30.3% |
36.3% |
40.1% |
| 3
[3500 HDD] |
30
|
13
|
19
|
5
|
16.1% |
17.9% |
25.3% |
27.2% |
| 4
[4500 HDD] |
30
|
13
|
19
|
7
|
12.5% |
14.0% |
21.6% |
23.7% |
|
|
|
|
|
|
|
|
|
| DOUBLE
PANE WOOD OR VINYL, LOW E, INERT GAS, & 1/2" AIR SPACE OR
TRIPLE PANE ( U = 0.43 R = 2.33 ) |
| 1
[1900 HDD] |
30
|
13
|
19
|
5
|
39.3% |
45.8% |
51.6% |
58.1% |
| 2
[2500 HDD] |
30
|
13
|
19
|
5
|
33.4% |
38.2% |
45.7% |
50.5% |
| 3
[3500 HDD] |
30
|
13
|
19
|
5
|
20.3% |
22.6% |
32% |
34.4% |
| 4
[4500 HDD] |
30
|
13
|
19
|
7
|
15.7% |
17.7% |
27.2% |
29.2% |
|
|
|
|
|
|
|
|
|
1. May use R-19 on
sloped ceilings and under HVAC equipment for up to 25% of ceiling area
2. Wall R-values represent
the sum of the wall cavity insulation plus insulating sheathing. 25% of
gross exterior wall area may have plywood, OSB,or gypsum (garage walls)
instead of insulating sheathing.
3. High
Heating means a furnace AFUE of 90% or more, or a heat pump HSPF of
7.8 or more. High Cooling means a SEER of 12 or more.High Heating
& Cooling means both heating and cooling equipment must meet
these minimum efficiencies.