|
New
Definitions
Wall Vented Crawl Space
Section R408
A foundation that uses foundation wall vents as a primary
means to control moisture. Insulation under the floor above
Closed Crawl Space Section R409
A foundation without wall vents that uses air sealed walls, ground and
moisture control, and mechanical drying potential
Conditioned Crawl Space Section R409
A foundation without wall vents that encloses an intentionally heated/
cooled space. Insulation at the walls.
Back to top
|
|
General
Requirements all Crawl Spaces
- R408.1.4- All drains and dryer
vents should terminate outdoors and be separate from gutters and foundation
drains
- R408.3- If outside grade is higher
than inside grade, the exterior should be dampproofed from the top of
the footing to the finished grade per R406.1
- R408.4- Building site graded to
drain water away from crawl space foundation per R403.1
- R408.8- Min. crawl space access
is 18x 24
- R408.9- Clean crawl space floor
of all vegetation and organic material. Remove wood forms and construction
materials prior to occupancy.
- R408.6- Seal all penetrations through
the subfloor with sealants not rockwool or fiberglass.
- R408.7- Seal all ductwork in the
crawl space with mastic or other approved system
Back to top
|
R408 renamed
Wall Vented Crawl Spaces
- Ground vapor retarders required
w/ drainage
- Vented crawls separated from basements,
porches & garages
- Floor and crawl duct sealing specified
Back to top
|
|
R318 Foam Plastic
Insulation
- In attics (where entrance is only
for service of utilities), foam plastic protection required:
1 ½-inch particleboard
¼-inch hardboard
3/8-inch gypsum board
Corrosion-resistant steel having a base
metal thickness of 0.016 inch
- Within crawl spaces, foam plastic
use is governed by R409.8.2
Back to top
|
|
408.1.1
Vented Crawl SpacesMinimum Vent Area
- Net area of ventilation openings
not less than 1 square foot per 150 square feet of crawl space ground
area
- Exception: Vent area may be reduced
to 1/1500 when the required openings are placed to provide cross-ventilation;
operable louvers are prohibited.
Back to top
|
|
R408.1.2
Foundation Vent Location
- 1 vent placed within 3 feet of
each corner of the building
- To prevent rainwater entry in a
crawl space built on a sloped site, the uphill foundation walls may
eliminate wall vent openings
- Vent dams when the bottom of the
foundation vent opening is less than 4 above the finished exterior
grade
Back to top
|
|
R408.1.3
Covering Material
- To prevent rodent entry, foundation
vents may be covered with any of these materials
Perforated sheet metal plates
not less than .07
Expanded sheet metal plates
not less than .047
Cast iron grills or grating
Extruded load-bearing brick
vents
Hardware cloth .035
wire or heavier
Corrosion-resistant mesh at
least 1/8 thick
Back to top
|
|
R408.1.5 Space
Separation
- Wall vented crawl spaces should
be separated from adjoining basements, porches and garages by a permanent
solid wall with all utility penetrations sealed
- Latched, weather stripped doors
or access panels provide entry to the crawl space and adjoining spaces
Back to top
|
|
R408.2 Ground
Vapor Retarders
- Required for all wall vented crawl
spaces
- Minimum 6-mil polyethylene or equivalent
over exposed earth with the joints lapped more than 12
- It is acceptable to puncture the
plastic at low spots for drainage
- Earth shall be sloped to a low
spot
Back to top
|
|
R409.1- Air Sealing
- R409.1- Seal holes through foundation
walls for supply and return ducts to outdoor packaged HVAC equipment,
if used.
- R409.1.1- Use air sealing caulk,
gaskets or sealants on the foundation wall and floor assemblies that
separate the crawl space from the outside and other ventilated areas
Back to top
|
|
R409.2.1- Polyethylene
Ground Cover
- R409.2.1- Install a minimum 6-mil
polyethylene vapor retarder or equivalent over exposed earth in crawl
space, with joints lapped more than 12
- Grade the crawl space floor so
that it drains to 1 or more low spots
- Install a drain to daylight or
sump pump at each low spot-- separately from gutter or foundation drains
Back to top
|
|
R409.2.2 Full
Interior Liners
- Ground vapor barrier can serve
as full interior liner by sealing edges to the walls and beam columns
- Stop top edge of wall liner 3
below top of foundationwall
- Bring top edge of wall liner up
interior columns or piers at least 4 above crawl space
Back to top
|
|
R409.2.1.1 Inspection
Gap at Top
- Provide a clear and unobstructed
3 minimum inspection gap between the top of the wall liner and
the bottom of the wood sill.
- Ignore possible energy penalty
posed by gap.
Back to top
|
|
R409.2.3 - Rat
Slabs
- The ground vapor retarder may be
protected against ripping and displacement by pouring an un-reinforced,
minimum 2 thick, concrete surface directly over the vapor barrier.
- Gravel not required
- Floor should be graded to drain
to one or more low spots
Back to top
|
|
409.5 Closed
Crawl Space Moisture Vapor Control Options
- Permanent dehumidifier
with electric outlet in crawl space
minimum capacity of 15 pints/ day
drain conden-sate to daylight or interior pump
- Supply air
1 cfm per 30 sq ft; backdraft damper required
No return air open to crawl space
Not considered a plenum air distribution system
- House air
1 cfm per 50 sq ft; fan rated for continuous duty
- Exhaust fan
1 cfm per 50 sq ft; fan rated for continuous duty
- Conditioned space with insulated
walls
Return air allowed
Foam plastic insulation on walls must be protected
by
approved thermal barrier
Back to top
|
|
409.6 Crawl
Spaces as HVAC Plenums
- Must meet NC Mechanical Code
- No plumbing cleanouts, gas lines,
other prohibited components
- Foam plastic insulation on walls
must be protected by approved thermal barrier
Back to top
|
|
409.7 Combustion
Air in Sealed Crawl Spaces
- Fuel burning appliances such as
furnaces and water heaters shall obtain combustion air from outside
Back to top
|
|
409.8.1
Closed Crawl Spaces, Foundation Wall Insulation
Where the floor above a closed crawl space is
not insulated, thewalls shall be insulated. Wall insulation can be located
on any combination of the exterior and interior surfaces and within the
structural cavities or materials of the exterior crawl space walls.
Wall insulation systems require that the band
joist area of the floor frame be insulated. Wallinsulation shall begin
3 inches below the top of the masonry foundation wall and shall extend
down to 3 inches above the top of the footing or concrete floor, 3 inches
above the interior ground surface or 24-inches below the outside finished
ground level, whichever is less. No insulation shall be required on masonry
walls of 9 inches height or less.
R409.8.1.1 Foam plastic termite inspection
gap.
For outside wall Section R324 governs applications. When expanded polystyrene,
extruded polystyrene, polyisocyanurate, or other foam plastic insulation
is installed on the inside surface of the exterior foundation walls, provisions
R409.8.1.1.1 2 below apply.
R409.8.1.1.1 Earth floored crawl spaces.
Provide a clear and unobstructed 3-inch minimum termite inspection gap
between the top of the foam plastic wall insulation and the bottom of
the wood sill. Because Insulation ground contact is not allowed, provide
a continuous 3-inch minimum clearance gap between the bottom edge of the
foam plastic wall Insulation and the earth floor surface.
Refer to N1102.1.7 to determine maximum allowances for insulation gaps.
R409.8.1.1.2 Concrete floor surfaced crawl
spaces.
Provide a clear and unobstructed 3-inch minimum termite inspection gap
between the top of the foam plastic wall insulation and the bottom of
the wood sill. Provide a continuous 3-inch minimum clearance gap between
the bottom edge of the
foam plastic wall Insulation and the concrete floor surface. Refer to
N1102.1.7 to determine maximum allowances for insulation gaps.
R409.8.1.2 Porous insulation materials.
When fiberglass, rockwool, cellulose or other porous insulation materials
are installed on the inside wall surface of a closed crawl space, provide
a clear and unobstructed 3-inch minimum termite inspection gap
between the top of the porous wall insulation and the bottom of the wood
sill. To reduce wicking potential, porous insulation ground contact is
not allowed in earth floored or concrete surfaced crawl spaces. Provide
a continuous 3-inch minimum wicking gap between the bottom edge of the
porous wall Insulation and the earth or
concrete floor surface. Refer to N1102.1.7 to determine maximum allowances
for insulation gaps.
Back to top
|
|
R409.8.2 Foam
Plastic Fire Safety
Foam plastic insulation may be installed
inside crawl spaces
without a thermal cover barrier or ignition barrier when the insulation
product has been tested in accordance with ASTM E 84 have a flame spread
rating of not more than 25 and a smoke developed rating of not more than
450 section R318.3. foam plastic tested in accordance with section R318.3
shall be installed according to the limitations stated in the ICC Evaluation
Service Evaluation Report (ICC-ES) for the product. Foam plastics that
have not been tested to meet these ratings shall be protected against
ignition by covering them with a thermal barrier.
Acceptable thermal barriers
include but are not limited to ½-inch cement board, metal foil
sheets, metal foil tape, steel or aluminum metal sheets or other approved
materials installed in such a manner that the foam is not exposed per
section R318.2.3.
Exception:
Foam plastic insulation located in closed crawl spaces used as conditioned
spaces as defined in section R409.5.5 Conditioned Space or section R409.6
Plenums shall be protected against ignition by an approved thermal barrier.
Back to top
|