North Carolina Code Changes Concerning Sealed Crawlspaces
Click here for the full text of the new crawl space code language

New Definitions

General Requirements all Crawl Spaces
R408 renamed Wall Vented Crawl Spaces
R318 Foam Plastic Insulation
408.1.1 Vented Crawl Spaces Minimum Vent Area
R408.1.2 Foundation Vent Location
R408.1.3 Covering Material
R408.1.5 Space Separation

R408.2 Ground Vapor Retarders

R409.1- Air Sealing
R409.2.1- Polyethylene Ground Cover
R409.2.2 Full Interior Liners
R409.2.1.1 Inspection Gap at Top
R409.2.3 - “Rat Slabs”
409.5 Closed Crawl Space Moisture Vapor Control Options
409.6 Crawl Spaces as HVAC Plenums
409.7 Combustion Air in Sealed Crawl Spaces
409.8.1 Closed Crawl Spaces, Foundation Wall Insulation
R409.8.2 Foam Plastic Fire Safety
Find out more about sealed crawlspaces in North Carolina by visiting www.crawlspaces .org Be sure to watch the great videos that explain this building concept in detail.

 

New Definitions

Wall Vented Crawl Space – Section R408
A foundation that uses foundation wall vents as a primary means to control moisture. Insulation under the floor above

Closed Crawl Space – Section R409
A foundation without wall vents that uses air sealed walls, ground and moisture control, and mechanical drying potential

Conditioned Crawl Space – Section R409
A foundation without wall vents that encloses an intentionally heated/ cooled space. Insulation at the walls.

Back to top

General Requirements all Crawl Spaces

  • R408.1.4- All drains and dryer vents should terminate outdoors and be separate from gutters and foundation drains

  • R408.3- If outside grade is higher than inside grade, the exterior should be dampproofed from the top of the footing to the finished grade per R406.1

  • R408.4- Building site graded to drain water away from crawl space foundation per R403.1

  • R408.8- Min. crawl space access is 18”x 24”

  • R408.9- Clean crawl space floor of all vegetation and organic material. Remove wood forms and construction materials prior to occupancy.

  • R408.6- Seal all penetrations through the subfloor with sealants – not rockwool or fiberglass.

  • R408.7- Seal all ductwork in the crawl space with mastic or other approved system

Back to top

R408 renamed Wall Vented Crawl Spaces
  • Ground vapor retarders required w/ drainage
  • Vented crawls separated from basements, porches & garages
  • Floor and crawl duct sealing specified

Back to top

R318 Foam Plastic Insulation

  • In attics (where entrance is only for service of utilities), foam plastic protection required:
       – 1 ½-inch particleboard
       – ¼-inch hardboard
       – 3/8-inch gypsum board
       – Corrosion-resistant steel having a base metal thickness of 0.016 inch
  • Within crawl spaces, foam plastic use is governed by R409.8.2

Back to top

408.1.1 Vented Crawl Spaces Minimum Vent Area

  • Net area of ventilation openings not less than 1 square foot per 150 square feet of crawl space ground area

  • Exception: Vent area may be reduced to 1/1500 when the required openings are placed to provide cross-ventilation; operable louvers are prohibited.

Back to top

R408.1.2 Foundation Vent Location

  • 1 vent placed within 3 feet of each corner of the building

  • To prevent rainwater entry in a crawl space built on a sloped site, the uphill foundation walls may eliminate wall vent openings

  • Vent dams when the bottom of the foundation vent opening is less than 4” above the finished exterior grade

Back to top

R408.1.3 Covering Material

  • To prevent rodent entry, foundation vents may be covered with any of these materials
         – Perforated sheet metal plates not less than .07”
         – Expanded sheet metal plates not less than .047”
         – Cast iron grills or grating
         – Extruded load-bearing brick vents
         – Hardware cloth .035” wire or heavier
         – Corrosion-resistant mesh at least 1/8” thick

Back to top

R408.1.5 Space Separation

  • Wall vented crawl spaces should be separated from adjoining basements, porches and garages by a permanent solid wall with all utility penetrations sealed

  • Latched, weather stripped doors or access panels provide entry to the crawl space and adjoining spaces

Back to top

R408.2 Ground Vapor Retarders

  • Required for all wall vented crawl spaces

  • Minimum 6-mil polyethylene or equivalent over exposed earth with the joints lapped more than 12”

  • It is acceptable to puncture the plastic at low spots for drainage

  • Earth shall be sloped to a low spot

Back to top

R409.1- Air Sealing

  • R409.1- Seal holes through foundation walls for supply and return ducts to outdoor packaged HVAC equipment, if used.

  • R409.1.1- Use air sealing caulk, gaskets or sealants on the foundation wall and floor assemblies that separate the crawl space from the outside and other ventilated areas

Back to top

R409.2.1- Polyethylene Ground Cover

  • R409.2.1- Install a minimum 6-mil polyethylene vapor retarder or equivalent over exposed earth in crawl space, with joints lapped more than 12”

  • Grade the crawl space floor so that it drains to 1 or more low spots

  • Install a drain to daylight or sump pump at each low spot-- separately from gutter or foundation drains

Back to top

R409.2.2 Full Interior Liners

  • Ground vapor barrier can serve as full interior liner by sealing edges to the walls and beam columns

  • Stop top edge of wall liner 3” below top of foundation wall

  • Bring top edge of wall liner up interior columns or piers at least 4” above crawl space

Back to top

R409.2.1.1 Inspection Gap at Top

  • Provide a clear and unobstructed 3” minimum inspection gap between the top of the wall liner and the bottom of the wood sill.

  • Ignore possible energy penalty posed by gap.

Back to top

R409.2.3 - “Rat Slabs”

  • The ground vapor retarder may be protected against ripping and displacement by pouring an un-reinforced, minimum 2” thick, concrete surface directly over the vapor barrier.

  • Gravel not required

  • Floor should be graded to drain to one or more low spots

Back to top

409.5 Closed Crawl Space Moisture Vapor Control Options

  • Permanent dehumidifier
    –  with electric outlet in crawl space
    –  minimum capacity of 15 pints/ day
    –  drain conden- sate to daylight or interior pump
  • Supply air
    –  1 cfm per 30 sq ft; backdraft damper required
    –  No return air open to crawl space
    –  Not considered a plenum air distribution system

  • House air
    –  1 cfm per 50 sq ft; fan rated for continuous duty

  • Exhaust fan
    –  1 cfm per 50 sq ft; fan rated for continuous duty

  • Conditioned space with insulated walls
    –  Return air allowed
    –  Foam plastic insulation on walls must be protected by
        approved thermal barrier

Back to top

409.6 Crawl Spaces as HVAC Plenums

  • Must meet NC Mechanical Code

  • No plumbing cleanouts, gas lines, other prohibited components

  • Foam plastic insulation on walls must be protected by approved thermal barrier

Back to top

409.7 Combustion Air in Sealed Crawl Spaces

  • Fuel burning appliances such as furnaces and water heaters shall obtain combustion air from outside

Back to top

409.8.1 Closed Crawl Spaces, Foundation Wall Insulation


Where the floor above a closed crawl space is not insulated, thewalls shall be insulated. Wall insulation can be located on any combination of the exterior and interior surfaces and within the structural cavities or materials of the exterior crawl space walls.

Wall insulation systems require that the band joist area of the floor frame be insulated. Wallinsulation shall begin 3 inches below the top of the masonry foundation wall and shall extend down to 3 inches above the top of the footing or concrete floor, 3 inches above the interior ground surface or 24-inches below the outside finished ground level, whichever is less. No insulation shall be required on masonry walls of 9 inches height or less.

R409.8.1.1 Foam plastic termite inspection gap.
For outside wall Section R324 governs applications. When expanded polystyrene, extruded polystyrene, polyisocyanurate, or other foam plastic insulation is installed on the inside surface of the exterior foundation walls, provisions R409.8.1.1.1 – 2 below apply.

R409.8.1.1.1 Earth floored crawl spaces. Provide a clear and unobstructed 3-inch minimum termite inspection gap between the top of the foam plastic wall insulation and the bottom of the wood sill. Because Insulation ground contact is not allowed, provide a continuous 3-inch minimum clearance gap between the bottom edge of the foam plastic wall Insulation and the earth floor surface.
Refer to N1102.1.7 to determine maximum allowances for insulation gaps.

R409.8.1.1.2 Concrete floor surfaced crawl spaces.
Provide a clear and unobstructed 3-inch minimum termite inspection gap between the top of the foam plastic wall insulation and the bottom of the wood sill. Provide a continuous 3-inch minimum clearance gap between the bottom edge of the
foam plastic wall Insulation and the concrete floor surface. Refer to N1102.1.7 to determine maximum allowances for insulation gaps.

R409.8.1.2 Porous insulation materials. When fiberglass, rockwool, cellulose or other porous insulation materials are installed on the inside wall surface of a closed crawl space, provide a clear and unobstructed 3-inch minimum termite inspection gap
between the top of the porous wall insulation and the bottom of the wood sill. To reduce wicking potential, porous insulation ground contact is not allowed in earth floored or concrete surfaced crawl spaces. Provide a continuous 3-inch minimum wicking gap between the bottom edge of the porous wall Insulation and the earth or
concrete floor surface. Refer to N1102.1.7 to determine maximum allowances for insulation gaps.

Back to top

R409.8.2 Foam Plastic Fire Safety

Foam plastic insulation may be installed inside crawl spaces
without a thermal cover barrier or ignition barrier when the insulation product has been tested in accordance with ASTM E 84 have a flame spread rating of not more than 25 and a smoke developed rating of not more than 450 section R318.3. foam plastic tested in accordance with section R318.3 shall be installed according to the limitations stated in the ICC Evaluation Service Evaluation Report (ICC-ES) for the product. Foam plastics that have not been tested to meet these ratings shall be protected against ignition by covering them with a thermal barrier.

Acceptable thermal barriers include but are not limited to ½-inch cement board, metal foil sheets, metal foil tape, steel or aluminum metal sheets or other approved materials installed in such a manner that the foam is not exposed per section R318.2.3.

Exception:
Foam plastic insulation located in closed crawl spaces used as conditioned spaces as defined in section R409.5.5 Conditioned Space or section R409.6 Plenums shall be protected against ignition by an approved thermal barrier.

Back to top